Specifications
Decription:
Square body US style high speed fuses.
Dimensions:
See dimensions illustration.
Ratings:
Volts:— 1250Vac (IEC) — 1300Vac (UL) Amps:— 50-1400A IR:— 100kA RMS Sym.
Agency Information:
CE, Designed and tested to IEC 60269: Part 4, UL Recognized. Consult Cooper Bussmann for UL Recognition/CSA Component Acceptance status.
Features and Benefits:
- Excellent dc performance
- Low arc voltage and low energy let-through (I2t)
- Low watts loss
- Superior cycling capability
Typical Applications:
- DC common bus
- DC drives
- Power converters/rectifiers
- Reduced voltage starters
Data Sheet:
Click here (Size 1*) Click here (Size 1) Click here (Size 2) Click here (Size 3)
Arc Voltage:
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Total Clearing I2t:
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Note:
- †Rated voltage (IEC) 1100. ‡Rated voltage (IEC) 1000V. ¥ UL Recognition at 1000V.
- Watts loss provided at rated current.
- Microswitch indicator ordered separately.
Power Losses:
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
| Catalog Number |
Size |
Rated Current RMS-Amps |
Clearing at 1000V - I2t (A2 Sec) |
Clearing at 1250V - I2t (A2 Sec) |
Watts Loss |
Dimensions (mm) Size B |
Dimensions (mm) Size C1 |
Dimensions (mm) Size C2 |
Dimensions (mm) Size D |
Dimensions (mm) Size E |
Dimensions (mm) Size H |
Dimensions (mm) Size I |
Pre-arc I2t (A2 Sec) |
Note |
| 170M3738 |
1* |
50 |
815 |
1100 |
15 |
156 |
130 |
101 |
59 |
45 |
20 |
10 |
135 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 400A Amps. |
| 170M3739 |
1* |
63 |
1300 |
1750 |
20 |
156 |
130 |
101 |
59 |
45 |
20 |
10 |
215 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 400A Amps. |
| 170M3740 |
1* |
80 |
2500 |
3350 |
25 |
156 |
130 |
101 |
59 |
45 |
20 |
10 |
420 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 400A Amps. |
| 170M3741 |
1* |
100 |
4450 |
5950 |
30 |
156 |
130 |
101 |
59 |
45 |
20 |
10 |
750 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 400A Amps. |
| 170M3742 |
1* |
125 |
9000 |
11500 |
35 |
156 |
130 |
101 |
59 |
45 |
20 |
10 |
1450 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 400A Amps. |
| 170M3743 |
1* |
160 |
16000 |
21000 |
40 |
156 |
130 |
101 |
59 |
45 |
20 |
10 |
2600 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 400A Amps. |
| 170M3744 |
1* |
200 |
31000 |
41000 |
45 |
156 |
130 |
101 |
59 |
45 |
20 |
10 |
5150 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 400A Amps. |
| 170M3745 |
1* |
250 |
54500 |
73000 |
55 |
156 |
130 |
101 |
59 |
45 |
20 |
10 |
9200 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 400A Amps. |
| 170M3746 |
1* |
315 |
115000 |
150000 |
60 |
156 |
130 |
101 |
59 |
45 |
20 |
10 |
18500 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 400A Amps. |
| 170M3747 |
1* |
350 |
165000 |
220000 |
65 |
156 |
130 |
101 |
59 |
45 |
20 |
10 |
27000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 400A Amps. |
| 170M4738 |
1 |
160 |
11500 |
15500 |
45 |
160 |
127 |
102 |
69 |
53 |
25 |
14 |
1900 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 500-630A Amps. |
| 170M4739 |
1 |
200 |
22500 |
30000 |
50 |
160 |
127 |
102 |
69 |
53 |
25 |
14 |
3800 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 500-630A Amps. |
| 170M4740 |
1 |
250 |
46000 |
61500 |
60 |
160 |
127 |
102 |
69 |
53 |
25 |
14 |
7750 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 500-630A Amps. |
| 170M4741 |
1 |
315 |
90000 |
120000 |
65 |
160 |
127 |
102 |
69 |
53 |
25 |
14 |
15000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 500-630A Amps. |
| 170M4742 |
1 |
350 |
125000 |
165000 |
70 |
160 |
127 |
102 |
69 |
53 |
25 |
14 |
20000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 500-630A Amps. |
| 170M4743 |
1 |
400 |
175000 |
235000 |
75 |
160 |
127 |
102 |
69 |
53 |
25 |
14 |
29500 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 500-630A Amps. |
| 170M4744 |
1 |
450 |
250000 |
335000 |
80 |
160 |
127 |
102 |
69 |
53 |
25 |
14 |
42000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 500-630A Amps. |
| 170M4745 |
1 |
†500 |
340000 |
- |
85 |
160 |
127 |
102 |
69 |
53 |
25 |
14 |
69500 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 500-630A Amps. |
| 170M4746 |
1 |
†550 |
465000 |
- |
95 |
160 |
127 |
102 |
69 |
53 |
25 |
14 |
95000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 500-630A Amps. |
| 170M4747 |
1 |
‡630 |
660000 |
- |
100 |
160 |
127 |
102 |
69 |
53 |
25 |
14 |
130000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 500-630A Amps. |
| 170M5738 |
2 |
250 |
38500 |
51500 |
65 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
6500 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5739 |
2 |
280 |
55500 |
74500 |
70 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
9350 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5740 |
2 |
315 |
77500 |
105000 |
75 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
13000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5741 |
2 |
350 |
97500 |
135000 |
80 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
16500 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5742 |
2 |
400 |
140000 |
180000 |
85 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
23000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5743 |
2 |
450 |
205000 |
270000 |
90 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
34000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5744 |
2 |
500 |
285000 |
380000 |
95 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
48000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5745 |
2 |
550 |
370000 |
495000 |
100 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
62000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5746 |
2 |
630 |
575000 |
730000 |
110 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
115000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5747 |
2 |
†700 |
795000 |
- |
115 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
160000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5748 |
2 |
†800 |
1200000 |
- |
120 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
245000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5749 |
2 |
‡900 |
1750000 |
- |
125 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
360000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M5750 |
2 |
‡1000 |
2350000 |
- |
135 |
160 |
127 |
102 |
77 |
61 |
25 |
14 |
480000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 630-1000A Amps. |
| 170M6738 |
3 |
315 |
5800 |
77500 |
185 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
9500 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| 170M6739 |
3 |
350 |
81500 |
110000 |
90 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
13500 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| 170M6740 |
3 |
400 |
120000 |
160000 |
95 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
19500 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| 170M6741 |
3 |
450 |
185000 |
245500 |
100 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
31000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| 170M6742 |
3 |
500 |
235000 |
310000 |
105 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
39000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| 170M6743 |
3 |
550 |
325000 |
435000 |
110 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
55000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| 170M6744 |
3 |
630 |
495000 |
665000 |
115 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
83500 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| 170M6745 |
3 |
700 |
705000 |
940000 |
120 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
115000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| 170M6746 |
3 |
800 |
995000 |
1300000 |
125 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
205000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| 170M6747 |
3 |
900 |
1500000 |
1900000 |
130 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
305000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| †170M6748 |
3 |
¥1000 |
2150000 |
- |
135 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
450000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| †170M6749 |
3 |
¥1100 |
2800000 |
- |
140 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
575000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| ‡170M6750 |
3 |
¥1250 |
3950000 |
- |
145 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
810000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
| ‡170M6751 |
3 |
¥1400 |
6000000 |
- |
150 |
159 |
128 |
101 |
92 |
76 |
36 |
16 |
1250000 |
1mm = 0.0394” / 1” = 25.4mm
Dashed lines (- - - - - -) apply to 800-1400A Amps. |
|